-40%

WEG CFW08 Variable Frequency Drive, 230 VAC, 16 Amps, 3-Phase, 5HP, NEMA 4X

$ 316.78

Availability: 100 in stock
  • All returns accepted: Returns Accepted
  • Condition: New
  • Refund will be given as: Money back or replacement (buyer's choice)
  • Return shipping will be paid by: Buyer
  • Modified Item: No
  • Country/Region of Manufacture: Brazil
  • Item must be returned within: 30 Days
  • Custom Bundle: No
  • Rated Load: 5 HP
  • Brand: WEG
  • Input Voltage: 230 V
  • MPN: CFW080160TDN4A1Z
  • Model: 10807877

    Description

    Description
    The WEG CFW08 series of drives feature the compact size of a microdrive with the full functionality of much larger drives. From extensive programmable control features to flexible mounting and display options, the CFW08 has everything one needs in a small, reliable drive package.
    The WEG CFW08 WASH Series is a redesign of our successful uline VFDs. Engineering improvements have produced one of the most compact and full featured microdrives in the marketplace.
    Outstanding features and options in a NEMA 4 enclosure allow the CFW08 WASH to be successfully used in a large variety of washdown applications.
    Overview
    Brand
    WEG
    Catalog Number
    CFW080160TDN4A1Z
    Input Power
    Three Phase - 230V
    Motor
    5 HP @ 230 V
    Nominal Drive AMPS
    16
    Braking Transistor
    Yes
    Frame Size
    A
    Dimensions (H x W x D)
    10.4” x 6.5“ x 8.5“
    Approximate Shipping Weight
    5 lbs
    Enclosure
    NEMA 4X
    UPC
    7894171786862
    Standard Features
    V/Hz and Sensorless Vector Control
    150% current overload capacity
    16 bit DSP controlled PWM output
    2.5 / 5 / 10 / 15 kHz adjustable swiching frequency
    Four isolated programmable digital inputs
    Two programmable relay outputs (1NO, 1NC, 240VAC 0.5 Amp
    Two isolated programmable analog inputs (0-10V, 0/4-20mA)
    Protective features:
    Over current
    motor overload
    drive over temperature
    output phase-to-phase and phase-to-ground short circuit
    DC bus over and under voltage
    external fault
    Control features:
    Linear and "S" ramp acceleration and deceleration
    local/remote control
    DC braking
    torque boost
    motor slip compensation
    electronic pot
    preset speeds
    adjustable V/Hz profile
    maximum and minimum adjustable frequency limits
    two skip frequencies
    adjustable output current limit
    JOG, ride-thru
    flying start and PID regulator
    Display readings:
    Motor speed
    frequency
    voltage
    current
    last fault
    heatsink temperature
    drive status
    Ambient: 32ºF (0ºC) to 104ºF (40ºC), 3300ft (1000m) altitude, 90% Humidity, Non-condensing
    SuperDrive (G1) Compatible
    Technical Data
    Power Supply
    Three Phase 200-240V (+10% / -15%)
    Frequency
    50 / 60 Hz +/-2 Hz
    Cos (Displacement Power Factor)
    Greater than 0.98
    Enclosure
    NEMA 4
    Control Modes
    V/Hz (Scalar)
    Sensorless Voltage Vector (VVW)
    Power Output
    Sinusoidal PWM (Space Vector Modulation)
    IGBT Transistors
    Switching Frequency
    2.5, 5, 10 or 15kHz
    Frequency Range
    0-300Hz
    Overload Capacity
    150% during 60 seconds, once every 10 minutes
    Control Inputs
    4 programmable isolated digital inputes, NPN or 24VDC logic (PNP)
    2 x programmable differential analog inputs, programmable for current or voltage
    Can be set as DI or as PTC input (0-10V, 4-20mA or 0-20mA)
    Control Outputs
    2 programmable relay outputs, one NO (Form A) and one NC (Form B): 250V /0.5A
    1x outputs with independent NO and NC at the same common
    1x output, programmable for voltage (0-10v) or current (0-20mA or 4-20mA) and with 0.25% linearity error
    Communication
    Serial: Optional RS-232 Serial Interface, RS-485 with external RS-232/485 Converter
    Fieldbus: Modbus RTU with external RS-232/485 Converter
    Protections
    Motor Over-Current
    Motor Overload
    Output Phase-to-Phase short circuit
    Output Phase-to-ground short circuit
    Programming Error
    DC Link over voltage
    DC link under voltage
    Drive over temperature
    External Fault
    Ambient Temperature
    32-104°F (40°C)
    up to 122°F (50°C) with 2% /1.8°F (1°C) output current derating
    Humidity
    5-90% Non Condensing
    Altitude
    0-3300ft (1000m)
    up to 13,200ft (4000m) with 10% /3300ft (1000m) output derating
    Regulatory Conformance
    EMC Directive 89 / 336 / EEC
    ENC61800-3
    LVD 73/23/EEC
    UL508C
    Special Functions
    Linear and “S” ramp accel and decel
    local/remote control
    FWD/REV selection
    DC braking
    manual and auto torque boost
    motor slip compensation
    electronic pot
    two skip frequencies
    maximum and minimum adjustable frequency limits
    adjustable output current
    PID Controller
    Keypad
    4 Digit display
    2 indicator LEDs
    8 keys
    Keypad Readouts
    output frequency (Hz)
    output current (A)
    output voltage (V)
    motor torque (%) in vector mode
    DC bus voltage (V)
    value proportional to frequency
    heatsink temperature
    fault
    status messages
    Mounting
    Surface Mounting with Screws
    Applications
    Pumps
    Fans
    Blowers
    Conveyors
    Rollout Tables
    Agitators
    Mixers
    Any Washdown Applications
    About this Product
    Main Characteristics
    Output current from 1.0 to 33 A (0.25 to 20 cv)
    Single or three-phase power supply
    Supply voltage from 200 to 480 V1)
    Vector (VVC) or scalar (V/F) control
    Accessories to expand functionalities
    Standard, Plus or Wash Versions (IP66/NEMA 4x)
    Multipump control
    Built-in operating and programming interface (HMI)
    Brake IGBT
    Internal (optional) or external (accessory) RFI filter
    Fault or alarm diagnosis
    Optional items for CANopen, DeviceNet, RS485 and RS232 industrial communication networks
    Remote operating interface - HMI (optional)
    Free SuperDrive programming software
    Applications
    Multimotors and multipumps
    Centrifugal pumps
    Process dosing pumps
    Fans / exhausters
    Stirrers / mixers
    Extruders
    Conveyor belts
    Roller tables
    Granulators / pelletizers
    Dryers / rotary ovens
    Rotary filters
    Winding machines / uncoiling machines
    Cutting and welding machines
    Special Functions and Resources
    Password to enable programming
    Fault self-diagnosis and auto-reset
    Indication of specific quantity (programmable) - (e.g.: m/min, rpm, among others)
    Slip compensation (V/F control)
    Adjustable quadratic and linear V/F curve
    Self-tuning routine (sensorless vector control)
    Dynamic braking
    Momentary speed impulse function (Jog)
    Copy of the setting via serial operating interface - HMI (copy function)
    Linear and “S” type ramps
    Independent acceleration and deceleration ramps
    DC braking (direct current)
    Multispeed function with up to 8 preset speeds
    Selection of the direction of rotation
    Overlapped PID control (automatic control of level, pressure, etc.)
    Start with the motor spinning (flying start)
    Rejection of critical or resonant frequencies (skip frequency)
    Operation during momentary network faults (ride-through)
    Communication protocols: Modbus-RTU, CANopen and DeviceNet
    Multipump Control
    The CFW08 version with multipump control board (A5 in the control board option in item 9 of the smart code) can control up to 4 pumps at the same time, keeping the output pressure constant, regardless of the flow demand. The CFW08 with multipump control board can also monitor the suction pressure and the source reservoir level, in addition to enabling the smart drive of the auxiliary pumps based on the running time.
    Connectivity
    Especially designed to integrate large industrial automation plants, the Fieldbus industrial communication networks provide advantages in the supervision, monitoring and control, generating high performance and great operating flexibility - ideal for applications on complex or integrated systems. The CFW08 can be interconnected to the industrial networks with worldwide used protocols: CANopen, DeviceNet, Modbus-RTU and Profibus-DP.
    a